TVA on Clean Line:  Economic and Reliability Issues

7/18/2014

12 Comments

 
Remember the letter to the TVA from Tennessee Congressmen Alexander and Fincher that asked some hard questions about Clean Line's Plains and Eastern Project?

The TVA has responded, and it's not looking good for Clean Line!  The letter, from TVA CEO William Johnson, is an exercise in reading between the lines, but here's my take on it, in a nutshell:

Clean Line is not economic for the TVA and presents reliability issues.
The answers to Alexander's and Fincher's questions are:
1. Does purchasing electricity from this distance increase security threats to TVA's
power supply? Former U.S. Secretary of State George Schultz has said we should
pay attention to generating more energy where we use it because of national
security risks.

The power grid is a complex, interconnected network of generating plants,
transmission lines, and distribution facilities. This system is designed with
redundancy and resiliency at its core to ensure a reliable electric power system.
Some increase in security risk is unavoidable as distance increases between
generation and point of use. The extra distance provides additional exposure for
natural or malicious events to force a transmission path out of service. The potential
for an interruption with long duration to power supply increases if full transmission network redundancy is not provided or as greater amounts of supply are obtained
from more remote sources. The Department of Defense has become aware of this
risk; it is implementing a program to make its major installations self-sustaining in
energy to mitigate the potential interruption from the grid.
Translation:  Yes.  The most reliable system is one where generation is located as close as possible to point of use.  Long transmission lines increase the opportunities for equipment failure, natural disaster, or terrorist activity.  Our military realizes this and has begun to island itself from the vagaries of our increasingly complex grid and long distance power shipments by building its own secure generation sources on site, which is known as distributed generation.
2. What is the cost of purchasing wind electricity compared to TVA generating or
purchasing other types of electricity generation?

TVA is studying the addition of new wind energy resources as part of the
development of its new Integrated Resource Plan (IRP). This process provides
opportunity for public participation. When TVA evaluates the cost of wind energy,
we include the value of the energy itself, as well as the cost to transmit out-of-valley
wind energy to the Tennessee Valley. In addition, there are costs associated with
the intermittent nature of wind generation. Through the IRP, TVA will rigorously
compare wind energy purchases against other alternative sources of energy
(renewables, new and existing TVA generating assets, or purchased power) to
serve local power companies and directly-served customers in a cost-effective
manner.
In FY2013, TVA's average fuel rates by asset type were as follows: nuclear,
$6/MWh; coal, $32/MWh; and gas, $39/MWh. The TVA average system fuel cost,
which includes hydro (no fuel cost) and purchased power, was $24/MWh. By
comparison, off-system wind purchases were $80/MWh (including transmission).
The cost of both wind and solar have trended steadily down in recent years. Lazard
Freres and Company, LLC, a leading financial advisory firm, does a periodic study
on the costs of renewable energy. Its most recent report states that the cost to
generate wind with the Federal production tax credit (PTC) is as low as $23 MWh;
without the credit, the costs are as low as $45 MWh. (Note that these are
production costs that do not take into account the cost of delivery to or the impact on
the TV A system.)
Translation:  Wind is the most expensive resource in TVA's portfolio of resources.  Wind without the PTC (and there currently is no PTC) costs $45 MWh to produce.  In order to get remote wind into TVA's system, Clean Line will add transmission costs that the company previously pegged at $25 MWh, for a total of $70 MWh.  This is a figure very generous to Clean Line, because it doesn't include any of the additional costs Clean Line is going to have to cover to pay for any necessary upgrades to TVA's transmission system to handle the injection of its generation.  TVA's $80 MWh price for remote wind is probably pretty accurate.  In addition, TVA says there are additional indirect costs due to wind's intermittent nature that must be considered.  All of this number crunching will occur as part of TVA's Integrated Resource Plan, which is still in process.  A decision on Clean Line is still a long way off.
3. There is substantial opposition in Congress to the wind production tax credit. Will
TVA ratepayers be at risk of increased rates if the wind production tax credit is not
renewed?

TVA does not benefit directly from the PTC. As noted in the prior response, the
PTC has a material impact on the cost structure of wind developers and, in turn, the
price they can offer to TVA or other purchasers of the wind energy. Any TVA
purchase of wind energy would be under a long-term contract that would place risk
associated with the tax credit on the seller.
Translation:  That would be the wind farm's problem because any contract TVA would sign would be for a fixed price.  If a lack of tax incentives makes building new wind farms uneconomic, then they won't be built!
4. What is the reliability of purchasing wind power as compared to other types of
electricity generated by natural gas, nuclear, coal, or hydropower?

Because wind is an intermittent resource that lacks some of the dispatch capability
of other resources, it does not eliminate the need for base load or dispatchable
power plants like nuclear, natural gas, coal and hydropower. Adding intermittent
generation resources like wind can be challenging to manage, particularly as the
volume of generation from those sources increases. Wind patterns are fairly
predictable, but not entirely so; in addition, weather and other factors can affect
output. To maintain reliability, a wind energy purchaser must keep adequate
capacity and spinning reserves to cover the variability inherent to wind. Spinning
reserve is typically calculated as the amount of capacity available to cover the loss
of the largest generation source on the system. Utilities across the country have
been integrating more wind into their systems over the last several years, and TVA
already integrates 1,515 megawatts of off-system wind power. The industry has
growing experience with this issue, but it does make ensuring reliability more
complex.
Translation:  Because wind is intermittent, it's not reliable.  TVA would have to pay to have reserve generation available at all times to make up for wind's unreliability.  In other words, buying wind would do little to shut down existing fossil fuel plants.
5. TVA's peak power demands tend to be between 4:00 p.m. and 7:00 p.m. and wind
tends to mostly blow at night. How does wind power fit into TVA's overall demand
structure if the electricity isn't being produced when TVA needs it the most?

TVA analyzes historic and forecasted wind patterns to determine expected wind
deliveries at our system peak. Our forecasting and planning processes reflect
adjustment to wind generation at our summer peaks based on this analysis. Clean
Line has told us that a production profile provided by the independent meteorology
firm, 3Tier Oklahoma, shows that panhandle wind energy produces at about a 50
percent capacity factor between the hours of 4:00 p.m. and 7:00 p.m., thus
contributing to meeting peak demand. TVA's current wind resources produced
about 25 percent average capacity factor over that peak period last summer, with
significant variation each day (between 5 and 65 percent capacity factor). TVA will
take the seasonal and time-of-day energy patterns of wind into account when
evaluating adding additional wind energy to its portfolio.
Translation:  Clean Line says its generation will be available 50% of the time, but reality and experience shows it will actually only be available 25% of the time, with extreme highs and lows.  When there are lows, the lights could go out if there isn't enough reserve generation ready to go (spinning).
6. At a roundtable in September 2013, hosted by Senators Corker and Alexander, you
said that TVA didn't need additional electricity generation capacity as the result of
reduced electricity demand. Has this projection changed?

Electricity demand is not expected to return to 2007 levels until the end of this
decade. We are projecting growth in demand of approximately 0.6 percent per year,
net of TVA's energy efficiency efforts. TVA believes that we have adequate
supplies to meet the near- to mid-term energy needs of the Valley reliably. Cleaner
energy sources, including nuclear, renewables, hydro and energy efficiency, provide
diversity within TVA's existing balanced energy portfolio. TVA is evaluating future
power needs and opportunities to meet them through the IRP. Wind and other
generating resources are regularly evaluated against existing or planned asset
additions to address changing conditions.
Translation:  Demand has tanked and is not expected to recover.
7. If the projection for TVA's electricity demand has changed since September 2013,
does it make more sense to purchase this wind power from Clean Line Energy
Partners, to build additional nuclear capacity, or to build additional natural gas or
coal capacity?

While demand over the next decade or so is predicted to be stable with low growth,
the TVA generation fleet is in transition. TVA has retired or will retire a substantial
portion of its coal fleet; we are committed to the completion of Watts Bar Nuclear
Plant Unit 2 and to a large new gas combined cycle plant in Paradise, Kentucky.
We have the potential to get incremental megawatts from the hydro system and a
significant amount from power uprates in the nuclear fleet. We have to either
retrofit, retire, or replace the Allen Plant in Memphis before 2019 under the terms of
an agreement with EPA and others. (Clean Line cannot supplant Allen because of
the need for a generation source physically located in that area to provide
transmission support that imported wind generation cannot provide.) In addition,
other market participants have approached TVA with expressions of interest to
provide electricity from gas, nuclear, wind and solar assets. TVA also factors in
energy efficiency and demand response programs into its resource decisions. The
recently announced draft 111 (d) rule from EPA, if enacted in its current form, will
also have a national impact on future decisions.
Clean Line will be evaluated in this context of low growth, transitioning fleet and
other options by application of the statutory mandate and guidance noted in the
preamble of this letter.
Translation:  In a word, no.  Clean Line isn't even a useful substitute for generation from coal plants that TVA is planning to close.  There are plenty of other resources available.

The rest of the questions deal with eminent domain questions, which TVA could have batted away entirely because TVA will not participate in those activities.  However, TVA answered each question with, "Clean Line said...." and repeated the same old carefully crafted lines about "voluntary acquisition," continued use of the properties for farming and ranching, and compensation in accordance with Clean Line's paid-for market value studies.  Read these answers using a falsetto voice for the things Clean Line said and you'll get a better appreciation for TVA's tongue-in-cheek repetition of Clean Line propaganda.

Bottom Line:  Clean Line needs to look elsewhere for customers for its Plains & Eastern payload.
12 Comments
Captain Trips
7/18/2014 02:55:20 am

When did you start working for TVA?

Reply
Keryn
7/18/2014 03:04:02 am

Today! I can't deny a letter that makes sense.

Reply
Aunt Bee link
7/18/2014 03:11:29 am

Yep, Amy. "This is about reliability."

Reply
Captain Trips
7/18/2014 03:45:10 am

Speaking of TVA and distributed gen and EE and how it plays into their Integrated Resource Plan (IRP)... If you already haven't done so (since you work for them now) - see the May 29 working group meeting slide deck here....
http://www.tva.com/environment/reports/irp/index.htm

Reply
Keryn
7/18/2014 03:55:12 am

Thanks, Cap'n. It's so hard to keep up with what my peons have been doing :-)

Reply
Keryn
7/18/2014 04:00:04 am

And, BTW, Cap'n., since you seem to know so much about resource planning, do you have a different take on the TVA letter? I'd love to hear it.

Reply
Captain T1:15
7/18/2014 05:09:35 am

No. Your interpretation, as well as the letter, was pretty clear.... except for your comment:

"Translation: Demand has tanked and is not expected to recover."

The letter talked about a steady, albeit small, growth rate in demand net of energy efficiency efforts. I would not have used the word "tanked". Yes demand dropped a bit due to the 2008-2009 recession, as it did across the country*, and the letter stated that they expect demand to slowly recover to 2007 levels by 2020.

* This is one of the reasons that your Stop PATH efforts were successful.


Reply
Keryn
7/18/2014 05:24:34 am

Thanks, Cap'n. I guess we'll have to agree to disagree on the reason for demand dropping off. But, you are correct, the TVA letter didn't say that... that was my spin. I think that as we move forward, energy efficiency demand management and distributed generation are going to have a more profound effect than planners are recognizing. Although, since planners aren't supposed to make mistakes that leave us in the dark and can't depend on hopes and dreams, they need to plan generously. I'm okay with that. I reserve the right to say... "I told you so" 20 years from now ;-) Because we'll both still be here, right?

Reply
Captain Trips
7/18/2014 05:38:34 am

No. I'll be dead in 20 years.

Reply
Keryn
7/18/2014 06:01:39 am

Well, I plan to haunt you through eternity as well. :-)

Captain
7/18/2014 06:06:12 am

Thank you!

Reply
Keryn
7/18/2014 06:10:38 am

I'll be the person with the pitchfork (as you might have guessed!)

Reply



Leave a Reply.

    About the Author

    Keryn Newman blogs here at StopPATH WV about energy issues, transmission policy, misguided regulation, our greedy energy companies and their corporate spin.
    In 2008, AEP & Allegheny Energy's PATH joint venture used their transmission line routing etch-a-sketch to draw a 765kV line across the street from her house. Oooops! And the rest is history.

    About
    StopPATH Blog

    StopPATH Blog began as a forum for information and opinion about the PATH transmission project.  The PATH project was abandoned in 2012, however, this blog was not.

    StopPATH Blog continues to bring you energy policy news and opinion from a consumer's point of view.  If it's sometimes snarky and oftentimes irreverent, just remember that the truth isn't pretty.  People come here because they want the truth, instead of the usual dreadful lies this industry continues to tell itself.  If you keep reading, I'll keep writing.


    Need help opposing unneeded transmission?
    Email me


    Search This Site

    Got something to say?  Submit your own opinion for publication.

    RSS Feed

    Archives

    June 2025
    May 2025
    April 2025
    March 2025
    February 2025
    January 2025
    December 2024
    November 2024
    October 2024
    September 2024
    August 2024
    July 2024
    June 2024
    May 2024
    April 2024
    March 2024
    February 2024
    January 2024
    December 2023
    November 2023
    October 2023
    September 2023
    August 2023
    July 2023
    June 2023
    May 2023
    April 2023
    March 2023
    February 2023
    January 2023
    December 2022
    November 2022
    October 2022
    September 2022
    August 2022
    July 2022
    June 2022
    May 2022
    April 2022
    March 2022
    February 2022
    January 2022
    December 2021
    November 2021
    October 2021
    September 2021
    August 2021
    July 2021
    June 2021
    May 2021
    April 2021
    March 2021
    February 2021
    January 2021
    December 2020
    November 2020
    October 2020
    September 2020
    August 2020
    July 2020
    June 2020
    May 2020
    April 2020
    March 2020
    February 2020
    January 2020
    December 2019
    November 2019
    October 2019
    September 2019
    August 2019
    July 2019
    June 2019
    May 2019
    April 2019
    March 2019
    February 2019
    January 2019
    December 2018
    November 2018
    October 2018
    September 2018
    August 2018
    July 2018
    June 2018
    May 2018
    April 2018
    March 2018
    February 2018
    January 2018
    December 2017
    November 2017
    October 2017
    September 2017
    August 2017
    July 2017
    June 2017
    May 2017
    April 2017
    March 2017
    February 2017
    January 2017
    December 2016
    November 2016
    October 2016
    September 2016
    August 2016
    July 2016
    June 2016
    May 2016
    April 2016
    March 2016
    February 2016
    January 2016
    December 2015
    November 2015
    October 2015
    September 2015
    August 2015
    July 2015
    June 2015
    May 2015
    April 2015
    March 2015
    February 2015
    January 2015
    December 2014
    November 2014
    October 2014
    September 2014
    August 2014
    July 2014
    June 2014
    May 2014
    April 2014
    March 2014
    February 2014
    January 2014
    December 2013
    November 2013
    October 2013
    September 2013
    August 2013
    July 2013
    June 2013
    May 2013
    April 2013
    March 2013
    February 2013
    January 2013
    December 2012
    November 2012
    October 2012
    September 2012
    August 2012
    July 2012
    June 2012
    May 2012
    April 2012
    March 2012
    February 2012
    January 2012
    December 2011
    November 2011
    October 2011
    September 2011
    August 2011
    July 2011
    June 2011
    May 2011
    April 2011
    March 2011
    February 2011
    January 2011
    December 2010
    November 2010
    October 2010
    September 2010
    August 2010
    July 2010
    June 2010
    May 2010
    April 2010
    March 2010
    February 2010
    January 2010

    Categories

    All
    $$$$$$
    2023 PJM Transmission
    Aep Vs Firstenergy
    Arkansas
    Best Practices
    Best Practices
    Big Winds Big Lie
    Can Of Worms
    Carolinas
    Citizen Action
    Colorado
    Corporate Propaganda
    Data Centers
    Democracy Failures
    DOE Failure
    Emf
    Eminent Domain
    Events
    Ferc Action
    FERC Incentives Part Deux
    Ferc Transmission Noi
    Firstenergy Failure
    Good Ideas
    Illinois
    Iowa
    Kansas
    Land Agents
    Legislative Action
    Marketing To Mayberry
    MARL
    Missouri
    Mtstorm Doubs Rebuild
    Mtstormdoubs Rebuild
    New Jersey
    New Mexico
    Newslinks
    NIETC
    Opinion
    Path Alternatives
    Path Failures
    Path Intimidation Attempts
    Pay To Play
    Potomac Edison Investigation
    Power Company Propaganda
    Psc Failure
    Rates
    Regulatory Capture
    Skelly Fail
    The Pjm Cartel
    Top Ten Clean Line Mistakes
    Transource
    Valley Link Transmission
    Washington
    West Virginia
    Wind Catcher
    Wisconsin

Copyright 2010 StopPATH WV, Inc.